当前位置: 首页 > 文章 > 变电所10kV电压互感器防谐振措施研究 农业科技与装备 2008 (4) 71-72
Position: Home > Articles > Measures on the Anti Resonance Using 10 kV Voltage Transformer in Substation Agricultural Science & Technology and Equipment 2008 (4) 71-72

变电所10kV电压互感器防谐振措施研究

作  者:
孙晓光;张德松
单  位:
盖州市农电局
关键词:
农业工程;变电所;铁磁谐振;消谐器;抗谐振PT
摘  要:
介绍盖州农电局66kV变电所内10kV电压互感器的运行情况和铁磁谐振过电压产生的机理,对当地运用的3种防铁磁谐振方法进行比对,结果表明:采用抗谐振型PT或在中性点串单相PT这两种装置,能有效抑制铁磁谐振。
译  名:
Measures on the Anti Resonance Using 10 kV Voltage Transformer in Substation
作  者:
SUN Xiaoguang, ZHANG Desong (Gaizhou Agriculture Bureau, Yingkou Liaoning 115200, China)
关键词:
agricultural engineering; substation; ferromagnetic-resonance; harmonic wave eliminator; anti-resonance PT
摘  要:
The operation conditions of 10kV voltage transformer in the 66kv substation in Gaizhou Agriculture Bureau and the generation mechanism of ferromagnetic-resonance overvoltage were introduced in the paper, and the three kinds of anti ferromagnetic-resonance methods were compared here as well. The results showed that: the two devices such as anti-resonance PT or neutral point connecting single-phase PT could control ferromagnetic-resonance effectively.